Acerca del producto
The GD-12 is typically installed in commercial facilities, warehouses, battery rooms or any areas where there is a potential for gas leasks, where there are gas appliances, areas through which gas pipes pass or where batteries are stored or charged.
Target gases are user selectable, and the GD-12 has on board output relays for Fan and Alarm, as well as a loop to connect to the Macurco DVP-120 control panel.
Macurco GD-12 Combustible Gas Detector Features:
- Detects Methane (natural gas), propane (LP), Hydrogen (H2)
- User can select target gases
- Mounts on 4x4 box
- Powered by 100-240VAC
- Fan Relay output: 5A, 240VAC, pilot duty, SPDT, latching or non latching
- Fan relay activation: OFF or 3-20% LEL
- Fan delay settings of 0, 1, 3, 5, 10 minutes
- Alarm relay output 0.5A 120V, selectable NO or NC
- Current loop, 4-20mA output for connection to DVP-120 panel
- Dimensions: 11.4 x 10.2 x 5.4 cm
- Operating Temperature -18C to 52C, 10-90% RH
- cETLus approved
Especificaciones técnicas
The GD-12 is typically installed in commercial facilities, warehouses, battery rooms or any areas where there is a potential for gas leasks, where there are gas appliances, areas through which gas pipes pass or where batteries are stored or charged.
Target gases are user selectable, and the GD-12 has on board output relays for Fan and Alarm, as well as a loop to connect to the Macurco DVP-120 control panel.
Macurco GD-12 Combustible Gas Detector Features:
- Detects Methane (natural gas), propane (LP), Hydrogen (H2)
- User can select target gases
- Mounts on 4x4 box
- Powered by 100-240VAC
- Fan Relay output: 5A, 240VAC, pilot duty, SPDT, latching or non latching
- Fan relay activation: OFF or 3-20% LEL
- Fan delay settings of 0, 1, 3, 5, 10 minutes
- Alarm relay output 0.5A 120V, selectable NO or NC
- Current loop, 4-20mA output for connection to DVP-120 panel
- Dimensions: 11.4 x 10.2 x 5.4 cm
- Operating Temperature -18C to 52C, 10-90% RH
- cETLus approved
Comparación de productos
Garantía del producto
Garantía estándar del fabricante según corresponda
Política de devoluciones
Garantía de precio
!00% siempre estamos por debajo del precio del mercado.
Explora colecciones de marca
Colecciones
Nuestros servicios


Alta ética e integridad empresarial
Cuenta la historia de tu marca a través de imágenes

Consistencia y rendimiento enfocado
Cuenta la historia de tu marca a través de imágenes

Visión compartida y éxito compartido
Cuenta la historia de tu marca a través de imágenes

Alta confidencialidad y seguridad
Cuenta la historia de tu marca a través de imágenes